Tab 1 · Practice questions
Free Texas journeyman electrician practice test, on the 2026 NEC.
Ten questions below, one from each subject area of the Journeyman NEC Knowledge exam, with the answer and the code section behind it. They come from the free part of the app, which has 763 in all.

Try 10 questions now
Answer each one, then open the answer. Keep the code book next to you: the exam is open book, and every answer names the section to look up.
01 · Definitions, Theory, and Plans
Where enclosures of switchboards, panelboards, motor control centers, and similar equipment are intended for specific locations, what does 110.28 require?
- A They shall be marked with an enclosure-type number as shown in Table 110.28
- B They shall be marked with the ingress protection rating from ANSI/IEC 60529
- C They shall be marked with the maximum ambient temperature of the location
- D They shall be marked with the name of the field evaluation body that tested them
Show the answer
Answer: A. 110.28. Table 110.28 is a selection table for ordinary locations only — the section says outright that it does not apply to hazardous (classified) locations, and that the enclosure is not meant to protect against condensation, icing, corrosion, or contamination arising inside. Article 100 defines Enclosure and points here for examples of the types.
NEC 2026, 110.28
02 · Services and Service Equipment
What must be done with a ground-fault protection system when it is first installed on site?
- A A qualified person shall performance test it by primary current injection, with a written record
- B It shall be visually inspected by the installer and the results reported to the utility
- C It shall be tested by the manufacturer before shipment and the certificate retained
- D It shall be tested by the authority having jurisdiction before the service is first energized
Show the answer
Answer: A. 230.95(E). Three details are all testable: the test is done on site when first installed, the method is primary current injection following the instructions supplied with the equipment, and a written record must be available to the authority having jurisdiction.
NEC 2026, 230.95(E)
03 · Feeders
Under Exception No. 3 to 215.4(A)(1), which feeder conductors are permitted to be sized at 100 percent of the combined continuous and noncontinuous load?
- A Grounded conductors that are not connected to an overcurrent protective device
- B Grounded conductors that are run in parallel in separate raceways
- C Ungrounded conductors terminated on equipment rated for 90 degree conductors
- D Equipment grounding conductors installed in a metal raceway or enclosure
Show the answer
Answer: A. Exception No. 3 to 215.4(A)(1). The 125 percent multiplier protects the terminals of an overcurrent device, so a grounded conductor that never lands on one does not need it. Do not confuse this with 215.4(B), a few lines below, which sets a separate minimum size for that same grounded conductor.
NEC 2026, 215.4(A)(1), Exception No. 3
04 · Branch Circuits and Conductors
For dwellings, outdoor outlets require GFCI protection where supplied by single-phase branch circuits rated 150 volts or less to ground and what maximum ampere rating?
- A 60 amperes or less
- B 50 amperes or less
- C 100 amperes or less
- D 30 amperes or less
Show the answer
Answer: A. 210.8(F) uses 60 amperes, the same ceiling as 210.8(D) and different from the 50 and 100 amperes of 210.8(B). Note also the replacement rule in the body of (F): if the equipment supplied by a covered outlet is replaced, the outlet has to be given GFCI protection — that is how the section reaches existing installations.
NEC 2026, 210.8(F)
05 · Wiring Methods and Materials
Under what condition are cable splices permitted to be located within a cable tray?
- A Where they are made and insulated by approved methods and remain accessible
- B Where the tray is a solid bottom type fitted with a solid metal cover
- C Where the tray is installed only in an industrial establishment under supervision
- D Where the splices are made in a listed box fastened to the bottom of the tray
Show the answer
Answer: A. 392.56, which covers cable splices and Type MV cable joints alike. The same section permits them to project above the side rails where they are not subject to physical damage. This is one of the places cable tray departs from a raceway: 300.15(A) forbids a splice or tap inside a raceway unless a listed section says otherwise, while a tray is a support system, not a raceway.
NEC 2026, 392.56
06 · Equipment and Devices
Within the required height of the working space, how far beyond the front of the electrical equipment may an associated support structure such as a concrete pad extend?
- A Not more than 150 mm (6 in.)
- B Not more than 300 mm (12 in.)
- C Not more than 75 mm (3 in.)
- D It may not extend beyond the front of the equipment at all
Show the answer
Answer: A. 110.26(A)(3). The height itself is the grade, floor or platform up to 2.0 m (6 1/2 ft) or the height of the equipment, whichever is greater, and only equipment or support structures associated with the electrical installation get the 150 mm (6 in.). A similar 150 mm shows up in 110.26(A)(4)(4) as the maximum side reach allowed past a ceiling structural member. Exception No. 3 lets a meter in its socket extend farther.
NEC 2026, 110.26(A)(3)
07 · Motors and Generators
Where a feeder supplies a motor load and other loads, the feeder protective device must have a rating not less than the sum of the other loads plus which value for two or more motors?
- A The rating permitted by 430.62
- B The rating permitted by 430.52
- C The rating permitted by 430.24
- D The rating permitted by 440.22
Show the answer
Answer: A. 430.63(3). This section is pure navigation, and the three pointers it lists are the answer: a single motor goes to 430.52, a single hermetic refrigerant motor-compressor goes to 440.22, and two or more motors go to 430.62. Notice the direction of the limit here — 430.63 sets a minimum rating, while 430.62 sets a maximum, so the two sections read as bookends. The exception sends you to 430.94 when that same feeder device is what protects a motor control center.
NEC 2026, 430.63
08 · Control Devices and Disconnecting Means
Which motor control circuit transformer is permitted to be protected by primary overcurrent devices, impedance limiting means, or other inherent protective means?
- A One under 50 volt-amperes that is integral to the controller and inside its enclosure
- B One under 50 volt-amperes that is mounted outside of the motor controller enclosure
- C One whose rated primary current is less than 2 amperes, wherever it is located
- D One whose primary device is set at not over 500 percent of rated primary current
Show the answer
Answer: A. 430.72(C)(3), and both conditions have to be met: under 50 VA and an integral part of the motor controller located within the controller enclosure. Do not blend it with the very next subsection, 430.72(C)(4), which handles a transformer whose rated primary current is under 2 amperes by allowing a primary device rated at not more than 500 percent of that current. The exception above them omits the protection entirely where opening the control circuit would create a hazard, as with a fire pump.
NEC 2026, 430.72(C)(3)
09 · Special Occupancies and Equipment
A legally required standby system shall make power available within the time required for the application, but in no case exceeding what maximum?
- A 60 seconds
- B 10 seconds
- C 30 seconds
- D 120 seconds
Show the answer
Answer: A. 701.12. Article 701 mirrors Article 700 section for section, so learn the pairs where the two differ. Transfer time is the first: 10 seconds in 700.12, 60 seconds here. Wiring separation is the second: emergency wiring must be independent under 700.10(B), while legally required standby wiring may share raceways with general wiring under 701.10(A). The loads themselves are described in the informational notes to 701.1.
NEC 2026, 701.12
10 · Renewable Energy Technologies
For an inverter output circuit, what value does 690.8(A)(1)(c) use as the maximum current?
- A The inverter continuous output current rating
- B The inverter continuous output current rating times 125 percent
- C The sum of the short-circuit currents of the modules feeding the inverter
- D The inverter maximum input current rating times 125 percent
Show the answer
Answer: A. 690.8(A)(1)(c). The three parts of 690.8(A)(1) each treat a different circuit: source circuits get the 125 percent of short-circuit current in (a), dc-to-dc converter circuits get the sum of parallel converter continuous output ratings in (b), and the inverter output takes the nameplate continuous output rating straight across in (c). The 125 percent for the inverter output circuit conductor still arrives later, through 690.8(B)(1).
NEC 2026, 690.8(A)(1)(c)
These 10 are the first free question of each Journeyman NEC Knowledge subject area in the app, as written for the app. The real exam has 59 items in 130 minutes; see how many questions the Texas journeyman test has.
Why the section matters
The Texas exam is open book. Knowing the answer helps, but finding it in the book under a clock is the actual skill. Every explanation ends with the 2026 section, so each question doubles as a lookup drill.
Today’s 5
Five questions a day, the same five all day, new ones tomorrow. They come from the full bank of 763, not only the free sample, and they keep a streak if you come back. Free for everyone.
Your misses come back
Every question you get wrong goes into a pile you can work through again until each one is right. That round is part of any pass.
The 15 subject areas
These are the areas in the content outlines that PSI uses to build the 11 Texas exams. Most of them run through every exam. A few belong to one or two licenses only.
| Area | Exams that test it |
|---|---|
| Definitions, Theory, and Plans | 9 of 11: all but the two Calculations portions |
| Calculations and Theory | The Journeyman and Master Calculations portions |
| Services and Service Equipment | 10 of 11 |
| Feeders | 10 of 11 |
| Branch Circuits and Conductors | All 11 |
| Wiring Methods and Materials | All 11 |
| Equipment and Devices | 10 of 11 |
| Motors and Generators | All 11 |
| Control Devices and Disconnecting Means | All 11 |
| Special Occupancies and Equipment | Journeyman, Master, Wireman, Maintenance, Industrial |
| Renewable Energy Technologies | Journeyman, Master, Wireman |
| Electric Signs and Outline Lighting | Master Sign and Journeyman Sign |
| Pools, Spas, and Fountains | Residential Appliance Installer |
| Transformers, Capacitors, and Surge Arresters | Journeyman Lineman |
| Electrical Safety | Journeyman Industrial |
Area names as the app shortens them. Which exams carry each one: the content outlines in the PSI Candidate Information Bulletin for TDLR Electrician, updated September 15, 2026.
How the questions are weighted in the real Journeyman exam, area by area: how many questions are on the Texas journeyman exam.
About the questions
Are these the real exam questions?
No. These are written for the app from the 2026 NEC and the TDLR outline, and they follow the two rules the bulletin sets for every question: ignore exceptions and optional methods unless the question asks, and treat conductors as copper unless it says otherwise.
Which code edition do they use?
The 2026 NEC. The PSI bulletin says the Texas exams are referenced to the 2026 edition from September 1, 2026.