Calculation · Article 120

A dwelling load calculation, step by step, on the 2026 NEC

The standard method for a one-family dwelling, worked from floor area to service rating, with the section to open at every step. This is one of the 24 calculations in the app, in full.

In short

  • Worked example A 2,400 ft² house with a 12 kW range, a 4.5 kW dryer, four fastened-in-place appliances, 10 kW of heat and a 6 kW air conditioner comes to 34,205 VA, 143 A at 240 V, so a 150 A service.
  • NEC 2026 In this edition the dwelling unit load is 2 VA/ft² (120.41), and load calculations live in Article 120.

The problem

A one-family dwelling has 2,400 ft² of habitable floor area, measured from the outside dimensions, not counting the detached garage or the open porch. It is served at 120/240 V, single-phase. It has two 20 A small-appliance circuits and one laundry circuit; a 12 kW freestanding range; a dryer nameplated 4.5 kW; a 4,500 VA water heater, a 1,200 VA dishwasher, a 900 VA disposer and a 1,400 VA built-in microwave, all fastened in place; 10,000 VA of fixed baseboard heat; and a 6,000 VA central air conditioner. Find the calculated load and the minimum service rating by the standard method.

The eight steps

  1. General lighting. Floor area × dwelling unit load.

    2,400 ft² × 2 VA/ft² = 4,800 VA

    Open 120.41. This one number covers every lighting outlet and every general-use receptacle of 20 A or less.

  2. Small-appliance and laundry circuits. 1,500 VA each.

    (2 × 1,500) + 1,500 = 4,500 VA

    Open 120.52(A) and (B).

  3. Demand on the lighting group. First 3,000 VA at 100%, the rest at the dwelling demand factor of Table 120.45, 35%.

    4,800 + 4,500 = 9,300 VA

    3,000 + (9,300 − 3,000) × 0.35 = 3,000 + 2,205 = 5,205 VA

  4. Range. Over 1¾ kW and not over 12 kW, so Table 120.55, Column C, one appliance: 8 kW, not the 12 kW nameplate.

    8,000 VA

  5. Dryer. Nameplate or 5,000 VA, whichever is larger (120.54). The nameplate is 4,500, so 5,000 governs.

    5,000 VA

  6. Appliances fastened in place. Four or more on the same service: 75% (120.53). The range, dryer, heat and air conditioning are excluded by the section’s own list.

    4,500 + 1,200 + 900 + 1,400 = 8,000 VA × 0.75 = 6,000 VA

  7. Heat or air conditioning, not both. Noncoincident loads (120.6): take the larger. Fixed electric heat is at 100% (120.51).

    10,000 VA heat > 6,000 VA A/C → 10,000 VA

  8. Total and service size. Add, divide by 240 V, and take the next standard rating at or above it (Table 240.6(A)).

    5,205 + 8,000 + 5,000 + 6,000 + 10,000 = 34,205 VA

    34,205 ÷ 240 = 142.52 A → 143 A → 150 A service

The trap: 2 VA, not 3

The 2026 edition puts the dwelling unit load for feeders and services at 2 VA/ft² in 120.41. The familiar 3 VA/ft² still exists, in 120.13, but it is for deciding how many branch circuits the house needs, not for the service calculation. Multiply by 3 here and a 2,400 ft² house picks up 2,400 VA it does not have.

The whole calculation in one table

LoadSectionVA
Lighting, small-appliance and laundry, after demand120.41, 120.52, Table 120.455,205
RangeTable 120.55, Col. C8,000
Dryer120.545,000
Fastened-in-place appliances at 75%120.536,000
Heat (larger than A/C)120.6, 120.5110,000
Total34,205

The app has 23 more like this, including the same house by the optional method, a six-unit feeder and an EV charger added to an existing service. The worked calculations.

Sources

  • NFPA 70, National Electrical Code, 2026 edition: 120.6, 120.13, 120.41, 120.45 and Table 120.45, 120.51, 120.52, 120.53, 120.54, Table 120.55, 230.79, Table 240.6(A). Section numbers cited; the code text is not reproduced.
  • The worked example is the app’s own, “One-family dwelling service, standard method”.